Series DGV is a normally-open valve that closes when liquid is present. Function is diagrammed in the series of illustrations below, from left to right...
First, at left, the valve is shown in a system with no liquid present. Gravity keeps the float down and the valve open. Air flows freely in and out.
In the second illustration, the system is operational and the pipelines are filled with liquid (shown as light blue). The polypropylene float rises with the liquid and the valve closes.
In the third illustration, the liquid is outgassing, and gas collects in the highest point of the system...where Series DGV is located.
Fourth illustration (below right) sufficient air or gas has accumulated, and the float drops. The valve now opens, and liquid pressure forces the air or gas through the vent. Once the gas is expelled, the float rises and again closes the valve. This process can repeat over and over, as often as gas occurs.
The valve has a very small orifice and is designed for trace amounts of gas. To expel large volumes of air such as at system start-up, see Series ARV. If your application requires expulsion of a large amount of air, as well as periodic venting of smaller amounts, you may require both the Series ARV and Series DGV.

| Available in Geon® PVC, Corzan® CPVC, Natural Polypropylene, Kynar® PVDF | |||||||
Pipe Size (NPT) |
|||||||
| DGV(series) 050(size) V(seal material) - PV(body material) Part numbers shown are FKM seals. For EPDM seals, change "V" to "EP." For example, DGV050EP-PV. • Standard connections are threaded. For other connection types, consult factory. |
|||||||
| Wetted Float Material for all Body Types: | Natural Polypropylene |
| Maximum Operating Pressure | 100 PSI |
| Minimum Specific Gravity | 0.9 |
Series DGV should be installed at the highest possible point in a piping system, and it must be oriented upright. In most cases, residual liquid and/or vapor in the valve may be expelled or "spit" from the outlet vent. Therefore, it is recommended to pipe the outlet port to a safe area for hazardous liquids, or use a standpipe for non-hazardous liquids.

For detailed installation instructions, please click here.
Please click here for .dwg type CAD file for Series DGV.
For specifications and catalog page in .PDF format, please click here.
Plast-O-Matic Valves, Inc.
1384 Pompton Avenue
Cedar Grove, NJ 07009 USA
Voice: (973) 256-3000
Fax: (973) 256-4745
Top